IL2530 – REVEXplus

Measuring device for testing of el. appliances based on ČSN 33 1600 ed. 2 standard; in conjunction with the WELDtest adapter it enables inspections and tests of arc welding equipment according to the requirements of the ČSN EN 60974-4 ed.3 standard.

The price includes a calibration certificate.

20 176  (16 674  excl. VAT)

The price is valid for the online shop only

Measurement:

  • Continuity by the current of > 200 mA
  • Insulation resistance with a voltage of 500 V
  • Leakage currents: by the substitude method, by the protective conductor and by the differential method
  • Leakage currents using a three-phase adapter or clamp meter
  • Active and apparent power input / current drawn by the appliance/power factor
  • Active and apparent power input / current / power factor by a clamp meter
  • Mains voltage

Other features:

  • Alternating quantities are measured using the TRMS method
  • Numerous monitoring and safety functions: automatic monitoring of the PE connection and the presence of voltage on PE, automatic monitoring of high leakage current
  • Inspections and tests of arc welding equipment in conjunction with the WELDtest adapter
  • Measurement of medical appliances in conjunction with the RM 2050 supplement

Package content:

  • REVEXplus measuring device
  • P2011 - safety connecting cable (banana/banana), black, length 2 m
  • P3011 - safety measuring tip, black
  • User´s manual
  • Calibration certificate
  • Warranty card

 

Generally:

  • Power supply: 230 V ± 10% / 50 Hz
  • Display: LED
  • Protection class: II (double insulation)
  • Overvoltage category: II / 300 V
  • Pollution degree: 2
  • Protection: IP 20
  • Dimensions: 150 x 195 x 50 mm
  • Weight: about 1 kg

Protective conductor resistance

  • Range: 0.000 Ω ÷ 20.00 Ω
  • Open circuit measuring voltage: 5 ÷ 12 V AC
  • Measuring current (R ≤ 2 Ω): ≥ 200 mA AC
  • Resistance compensation of test leads: yes (up to 2 Ω)

Insulation resistance:

  • Range: 0.0 kΩ ÷ 100.0 MΩ
  • Nominal voltage: 500 V DC
  • Nominal current: ≥ 1 mA DC

Current passing through the protective conductor

  • Range: 0.000 mA ÷ 10.00 mA

Differential current

  • Range: 0.000 mA ÷ 10.00 mA

Substitute leakage current

  • Range: 0.000 mA ÷ 20.00 mA
  • Open circuit measuring voltage: 230 V ± 15% / 50 Hz
  • Max. measuring current: 3.5 mA

Leakage current through external measuring device

  • Range: 0.00 mA ÷ 20.0 mA

Touch current

  • The technical parameters are identical to the selected measurement method.

Active, apparent power

  • Range: 5 W, VA ÷ 3680 W, VA

Power factor

  • Range: 0.00 ÷ 1.00

Current passing through the appliance

  • Range: 0.00 A ÷ 16.00 A

Current measured by a clamp meter

  • Range: 0.00 A ÷ 100.0 A

Power factor measured by a clamp meter

  • Range: 0.00 ÷ 1.00

Active power input, apparent power input measured by a clamp meter

  • Range: 10 W, VA ÷ 9999 W, VA

Network Voltage

  • Range: 207.0 V ÷ 253.0 V

 

User´s Manual

Download(638 KB)