IL2531 – REVEXplus USB
Measuring device for testing of el. appliances based on ČSN 33 1600 ed. 2 standard; in conjunction with the WELDtest adapter it enables inspections and tests of arc welding equipment according to the requirements of the ČSN EN 60974-4 ed.3 standard.
The measurement results can be transmitted on-line to a connected PC – making the REVEXplus USB ideal tester for services or production lines.
Note: The device does not have a memory for storing measurement results.
The price includes the calibration certificate.
21 115 Kč (17 450 Kč excl. VAT)
The price is valid for the online shop only
Measurement
- Continuity with the current of > 200 mA
- Insulation resistance with a voltage of 500 V
- Leakage currents: by the substitude method, by the protective conductor and by the differential method
- Leakage currents using a three-phase adapter or clamp meter
- Active and apparent power input / current drawn by the appliance / power factor
- Active and apparent power input / current / power factor by a clamp meter
- Mains voltage
Other features
- Alternating quantities are measured using the TRMS method
- Numerous monitoring and safety functions: automatic monitoring of PE connection, the presence of voltage on PE, automatic monitoring of high leakage current
- Inspections and tests of arc welding equipment in conjunction with the WELDtest adapter
- Measurement of medical appliances in conjunction with the RM 2050 supplement
- Possibility to connect to PC (only on-line data transfer without the possibility of storing in the device's memory)
Package content
- REVEXplus USB measuring device
- P2011 - safety connecting cable (banana/banana), black, length 2 m
- P3011 - safety measuring tip, black
- User´s manual
- USB cable
- Calibration certificate
- Warranty card
Generally
- Power supply: 230 V ± 10% / 50 Hz
- Display: LED
- Protection class: II (double insulation)
- Overvoltage category: II / 300 V
- Pollution degree: 2
- Protection: IP 20
- PC Connection: USB
- Dimensions: 150 x 195 x 50 mm
- Weight: about 1 kg
Protective conductor resistance
- Range: 0.000 Ω ÷ 20.00 Ω
- Open circuit measuring voltage: 5 ÷ 12 V AC
- Measuring current (R ≤ 2 Ω): ≥ 200 mA AC
- Resistance compensation of test leads: yes (up to 2 Ω)
Insulation resistance
- Range: 0.0 kΩ ÷ 100.0 MΩ
- Nominal voltage: 500 V DC
- Nominal current: ≥ 1 mA DC
Current passing through the protective conductor
- Range: 0.000 mA ÷ 10.00 mA
Differential current
- Range: 0.000 mA ÷ 10.00 mA
Substitute leakage current
- Range: 0.000 mA ÷ 20.00 mA
- Open circuit measuring voltage: 230 V ± 15% / 50 Hz
- Max. measuring current: 3.5 mA
Leakage current through the external measuring device
- Range: 0.00 mA ÷ 20.0 mA
Touch current
- The technical parameters are identical to the selected measurement method.
Active, apparent power
- Range: 5 W, VA ÷ 3680 W, VA
Power factor
- Range: 0.00 ÷ 1.00
Current passing through the appliance
- Range: 0.00 A ÷ 16.00 A
Current measured by a clamp meter
- Range: 0.00 A ÷ 100.0 A
Power factor measured by a clamp meter
- Range: 0.00 ÷ 1.00
Active power input, apparent power input measured by a clamp meter
- Range: 10 W, VA ÷ 9999 W, VA
Network Voltage
- Range: 207.0 V ÷ 253.0 V